Engineering documentation

Spec matrix, IEC type-tests, MV screen design.

Nine cable families, 80+ rows of conductor-class-aware spec data, four MV voltage tiers (6/10 → 26/35 kV) with IEC 60502-2 screen design, and eight type-test reports from CESI / DNV KEMA / TÜV Rheinland. Each row plugs straight into a single-line diagram review.

Sample row · YJV22 MV

What a bid-grade row looks like.

Open full deep-dive matrix
SizeClassODWeightAir 30°CBuriedRdc20Rac90XIsc 1 s
YJV22 3×185 mm² (12/20 kV)Class 2 strandedØ 74.8 mm ± 1.08,068 kg/km404 A380 A0.0991 Ω/km0.127 Ω/km0.108 Ω/km26.5 kA

XLPE 5.5 mm + inner/outer semi-con 0.6 mm + 25 mm² copper-tape screen · PD ≤ 10 pC at 2 U₀ · GB/T 12706.4-2008 / IEC 60502-2. Bend radius 15 × OD = 1,122 mm. Buried at 0.7 m, soil ρ = 2.5 K·m/W. Methods E / D / B2 per IEC 60364-5-52.

Spec matrix · 9 families

80+ rows · 4 voltage tiers · 8 correction factors per family.

0.6/1 kV

YJV 0.6/1 kV power cable

XLPE (cross-linked polyethylene) · Unarmoured (steel-tape variant → YJV22)

17 rows · IEC 60502-1 · GB/T 12706.1-2008

IEC 60502-1GB/T 12706.1-2008SNI IEC 60502-1:2009

0.6/1 kV (LV) · 6/10 kV (MV)

YJV22 0.6/1 kV & 6/10 kV steel-tape armoured

XLPE · Galvanized steel-tape (STA) double-layer overlap

19 rows · IEC 60502-1 · IEC 60502-2

IEC 60502-1IEC 60502-2GB/T 12706.1-2008

450/750 V

BV / BVR 450/750 V copper building wire

PVC TI1 · Not applicable

12 rows · IEC 60227-3 · GB/T 5023.3

IEC 60227-3GB/T 5023.3SNI 04-6629.3:2006

450/750 V

BVVB flat 450/750 V building cable

PVC TI1 cores · Not applicable

8 rows · IEC 60227-4 · GB/T 5023.4

IEC 60227-4GB/T 5023.4JB/T 8734.5-2016

300/500 V

RVV 300/500 V flexible cable

PVC TI2 cores · Not applicable

9 rows · IEC 60227-5 · GB/T 5023.5

IEC 60227-5GB/T 5023.5SNI 04-6629.5:2006

450/750 V

WDZA-GYJS(F)/125 °C LSZH safety wire

Double-layer irradiated cross-linked halogen-free low-smoke compound · Not applicable

7 rows · JG/T 441-2014 · IEC 60332-3

JG/T 441-2014IEC 60332-3IEC 61034-2

450/750 V

KVV / KVVR / KVVRP / KVV22 control cable

PVC or XLPE (per family) · Shield (KVVRP) · steel-tape (KVV22) · plain (KVV)

9 rows · GB/T 9330.1-2020 · GB/T 9330.2-2020

GB/T 9330.1-2020GB/T 9330.2-2020IEC 60227-7 signal

Data (PoE+ supported on Cat6 with bundling derating)

Cat5e / Cat6 industrial LAN cable

Polyethylene (PE) per pair · Optional foil/braid shield (F/UTP / SF/UTP)

3 rows · TIA/EIA-568-C.2 · ISO/IEC 11801

TIA/EIA-568-C.2ISO/IEC 11801YD/T 1019-2013

0.6/1 kV

YFD prefabricated branch cable

XLPE · Optional steel-tape; molded-joint factory pre-cast

4 rows · JB/T 10743-2007 · Project drawing schedule required

JB/T 10743-2007Project drawing schedule required

IEC type-test reports

CESI · DNV KEMA · TÜV Rheinland.

Specimen · NDA-gated

The lab, standard, and scope for each report below are fixed; the report number, issue date, and signed PDF are released on issuance, under NDA, at first qualified RFQ. The verify-portal links below open each lab's public lookup so buyers can cross-reference the issued number.

MV scope today. Current MV bid scope: 6/10 kV — IEC 60502-2 type-test on file, Class 2 and Class 5 conductors, 12-bracket spec matrix below. YJV22 12/20 kV rows are referenced against IEC 60502-2 standard construction and are in coordinated re-test for per-voltage-class confirmation; useful for engineering preview, but anchor 12/20 kV tender prequalification on the confirmed per-voltage-class scope (release timeline in /about).

IEC 60502-1 (2004) + A1 (2009)

Type tests on YJV 0.6/1 kV XLPE-insulated power cable: tensile strength, elongation, thermal aging, hot-set, water absorption, AC voltage 3.5 kV / 5 min, partial discharge, bending + tan δ, heating cycle.

Report no.
Specimen — issued under NDA
Lab
CESI S.p.A. · Milan, Italy

IEC 60502-2 (2014)

Type tests on YJV22 6/10 kV three-core armoured cable: partial discharge ≤ 10 pC at 2 U₀, AC voltage 6.5 kV (U₀) for 5 min, impulse withstand 95 kV peak, screen system continuity, 8-hour heat cycle, water absorption.

Report no.
Specimen — issued under NDA
Lab
CESI S.p.A. · Milan, Italy

IEC 60228 (2004)

Conductor resistance verification — Class 1 solid, Class 2 stranded, Class 5 flexible compliance for sections 1.5 → 240 mm². Resistance measured at 20 °C and corrected to 20 °C ambient.

Report no.
Specimen — issued under NDA
Lab
CESI S.p.A. · Milan, Italy

IEC 60331-1-2 (2018)

Fire-resistance test at 750 °C for 180 minutes with mechanical impact at 5 min intervals. Circuit continuity verified across the full burn cycle on 4×2.5 mm² sample.

Report no.
Specimen — issued under NDA
Lab
DNV KEMA Laboratories · Arnhem, Netherlands

IEC 60332-3-24 (Category C)

Flame propagation test on bunched cables (Category C — bundled 1.5 L/m of non-metallic material): no flame propagation beyond 2.5 m above burner after 20 minutes burner application.

Report no.
Specimen — issued under NDA
Lab
DNV KEMA Laboratories · Arnhem, Netherlands

IEC 61034-2 (2019)

Smoke density on burning cable: minimum 60 % light transmittance under steady-state burn conditions, 3 m cube test chamber, measurement at 0.6 m height.

Report no.
Specimen — issued under NDA
Lab
TÜV Rheinland · Köln, Germany

IEC 60754-1 (2019)

Determination of halogen acid gas (HCl + HBr) content of materials taken from the cable insulation and sheath: result < 5 mg/g (LSZH compound compliance).

Report no.
Specimen — issued under NDA
Lab
TÜV Rheinland · Köln, Germany

IEC 60754-2 (2019)

Determination of degree of acidity (pH) and conductivity of combustion gases from cable materials: pH ≥ 4.3 and conductivity ≤ 10 μS/mm.

Report no.
Specimen — issued under NDA
Lab
TÜV Rheinland · Köln, Germany

IEC 60502-2 (2014)

Type tests on YJV22 12/20 kV three-core armoured cable: partial discharge ≤ 10 pC at 2 U₀, AC voltage 21 kV (U₀) for 5 min, impulse withstand 125 kV peak, screen system continuity, 8-hour heat cycle, water absorption. Pending coordinated re-test against the 6/10 kV specimen entry.

Report no.
Pending issuance — coordinated re-test required for 12/20 kV scope
Lab
CESI S.p.A. (target) · Milan, Italy

Trust posture

Engineering claims stay datasheet-gated.

Construction stack

Outer sheath, insulation, conductor, shield or armor — buyer-readable layers.

Order package

Coils, 305 m boxes, drums, end caps, and handling cues.

Route risk

Buried runs, tunnels, trays, control cabinets, risers tied to family selection.

Document gate

Certificate wording, test reports, payee, model coverage stay verified before order.

Next page

See commercial terms, channel split, wholesale FOB, Indonesia readiness.

Commerce →